BS version, Form 4. Opens with an example board; change anything and the layout updates.
Each board is priced on its own discount. Reconnect and test is set once for the project (region and number of visits) and is not discounted. The customer details, price list and PDF options are shared by every board in the project.
Adds this % of the equipped ways as spaces (no device), sized like the devices. If the board still has less spare than this, empty sections are added until it reaches it.
Every bit of empty height in a stack, group mounted section or pan is filled with spaces (400, 300 or 200 mm in a compartment, 140 or 120 mm group mounted, or a spare pan way) and priced, because a spare has to be physically fitted. Untick only to see the bare layout.
Each circuit picks the lowest catalogue breaking capacity that meets this, unless you choose one in the circuit schedule. Together with In and poles this gives the Hager catalogue number (P160 with cable terminals, P250 and P630 with front connection).
Each one is its own section. Give them names such as Mains and Generator. Left, centre or right sets where each sits; sections sharing a position follow the order listed here.
Mounting "Auto" follows the form of separation. "Compartment" forces a P160 or P250 out of the group mounted section. Single-pole devices are marked SP and switch disconnectors SD. Fuse switches fed from the incomer live side are drawn red, marked LS, and placed in the stack next to the incomer. Metered is how many of that line have a meter, shown as an M on the drawing. "Goes in" puts a line in a particular cubicle (letter and name as on the drawing) or, with a bus coupler, anywhere on one side of it; each side is worked out from where the coupler actually sits, so moving the coupler or sections keeps devices on the right side. A PW1 MCCB takes its own 450 or 700 mm section; click it on the drawing to set its size (630 to 1600 A). An ACB (own section) is the same as an incoming ACB: 800 to 4000 A, 700 mm wide (900 mm for 3200 A and up), with the same frame, breaking capacity, poles, drawout or fixed and trip unit choices. A space is an empty way with no device: 200 mm or 300 mm in a compartment, or a 140 mm way (big enough for a P250) when a 200 mm space goes group mounted. The Spaces % in the Board panel adds more on top, sized like the equipped devices.
Click a section on the drawing to see and change its properties, or to move it left or right. A section you add goes to the right of the selected one (or on the end if none is selected).
Name each circuit and set the rated current (In) of its device. The names and ratings follow the device if it moves, and appear on the drawing, the single-line diagram and the PDF schedule. Incomers are named in their own card above.
Every Hager catalogue number on this board: incomers and couplers (hw+ ACB or PW1600), PW1 and ACB outgoing, and each outgoing MCCB once its In is set in the circuit schedule. Internal only, not on the customer PDF.
Drawn from the layout: incomers, bus couplers, the main busbar, group mounted distribution busbars and every outgoing way with its compartment reference.
Internal only: the discount, trade prices and price list never appear on the customer PDF. The PDF shows the net total only. With stockist cover, the stockist price is the net total and the contractor price is the stockist price plus the cover (on the boards only, not on reconnect and test); choose which one prints under PDF output.
Prints in a highlighted box on this board's general arrangement page. Project notes print once, on the project overview (page 1); a single board's PDF has no overview, so they print beside these.